Mai Canjin Kayan Aikin Inji
Mai zuwa shine cikakken siga na wannan taswira. Hakanan zamu iya keɓancewa gwargwadon bukatun abokin ciniki.
1, Transformer tushen: JB/T5555-2013.
2, JBKSarrafa Transformer
3, Lokacin da rated shigar da ƙarfin lantarki ne AC 380V-427V-480V 50Hz, da babu-load halin yanzu ne kasa da 12% na rated halin yanzu.
4. Rated fitarwa ƙarfin lantarki: U = 115V 275VA.
5. Matsayin insulation shine Class B.
6, Hi-Pot Gwajin: Firamare, Sakandare-Core 2000V 5S <3mA;Firamare-Secondary 2000V 5S
7, Insulation juriya: Primary, Secondary-Core ≥100MΩ 1000V DC;Primary-Secondary ≥100MΩ 1000V DC
8, Zazzabi Yunƙurin: The zazzabi Yunƙurin na gidan wuta a karkashin rated load ne kasa da 80K.
9, Transformer aiki yanayi: na cikin gida Altitude≤2000M
10. Yanayin zafin jiki: -5 ℃ - 40 ℃
11, Gabaɗaya Girma: Kamar yadda aka nuna a cikin adadi na sama.
An yi fenti gaba ɗaya tafsiri, kuma baƙin ƙarfe ba shi da tazarar iska